A physical Emergency Stop pushbutton is wired normally closed (NC) to PLC input I:0/1. To make a rung stay true while the E-Stop is NOT pressed and drop out if the button is pressed or the wire breaks, which instruction should be placed in series on the rung?

  1. An XIO instruction addressed to I:0/1
  2. An XIC instruction addressed to I:0/1
  3. An OTL latch instruction addressed to I:0/1
  4. An OTE coil instruction addressed to I:0/1
Show the answer

B. An XIC instruction addressed to I:0/1

Because the NC contact holds input I:0/1 at 1 during normal operation, an XIC instruction evaluates true while healthy and turns false if the button opens or the wire breaks (fail-safe). Using XIO would invert the logic and allow operation on a broken wire.

Reference: NFPA 79 Chapter 9 (Control Circuits and Control Functions)

In a standard 3-wire motor start-stop seal-in rung, what happens if the momentary Start button is released after the motor output coil energizes?

  1. The motor stops at once and stays off until the Start button is pressed and held again
  2. The PLC enters fault mode due to a parallel branch
  3. A parallel contact tied to the output coil keeps the rung energized
  4. The Stop contact automatically latches into a closed state
Show the answer

C. A parallel contact tied to the output coil keeps the rung energized

The seal-in (holding) contact in parallel with the Start contact is addressed to the motor output coil itself. Once energized, it maintains power flow around the released Start button until the Stop contact or overload opens the rung.

Reference: IEC 61131-3 Section 4; NFPA 79 Section 9.2

How does a Retentive Timer On-Delay (RTO) differ from a standard Timer On-Delay (TON) when its rung goes false before the preset time is reached?

  1. The RTO resets its accumulated value to zero immediately
  2. The RTO keeps counting upward the whole time the rung is false, until it reaches its preset
  3. The RTO sets its Done bit high as soon as the rung turns false
  4. The RTO retains its accumulated value until explicitly cleared by a Reset instruction
Show the answer

D. The RTO retains its accumulated value until explicitly cleared by a Reset instruction

A standard TON clears its accumulated time to zero whenever the rung goes false. An RTO holds its accumulated count across rung interruptions and power cycles until a separate RES (Reset) instruction clears it.

Reference: IEC 61131-3 Section 2.5 (Standard Function Blocks)