Sample questions
In NFPA 79 and ISO 10218-1, how does a Category 1 stop differ from a Category 0 stop?
Category 1 cuts servo power immediately without braking, while Category 0 ramps down smoothly
Category 1 uses controlled servo deceleration to bring the robot to a stop along its path before removing actuator power, whereas Category 0 removes power immediately
Category 1 is used only in manual T1 mode, whereas Category 0 is used only in AUTO mode
Category 1 keeps servo power energized indefinitely while holding position
Show the answer
B. Category 1 uses controlled servo deceleration to bring the robot to a stop along its path before removing actuator power, whereas Category 0 removes power immediately
A Category 0 stop removes power immediately and engages mechanical brakes, which can cause a heavy arm to deviate from its path. A Category 1 stop uses controlled electrical braking to stop quickly on path and then removes actuator power.
Before entering a caged robot cell to replace a worn pneumatic gripper valve and clean a servo motor brake, which energy sources must be isolated and locked out under OSHA 29 CFR 1910.147?
Only the 480 VAC electrical disconnect, because pneumatic air vents automatically
Only the teach pendant E-Stop button, because it is dual-channel
All hazardous energy sources, including electrical power, compressed air (bled to zero), and gravitational/stored energy in raised arms
Only the PLC Ethernet switch so no new commands arrive
Show the answer
C. All hazardous energy sources, including electrical power, compressed air (bled to zero), and gravitational/stored energy in raised arms
OSHA 1910.147 requires isolating and locking out every hazardous energy source—electrical, pneumatic/hydraulic (with residual pressure bled), and mechanical/gravitational (blocking raised arms or tooling)—and verifying zero energy. An E-Stop is a control circuit, never an energy-isolating device.
Reference: OSHA 29 CFR 1910.147(c)(4) & (d) (Control of Hazardous Energy — LOTO)
Why is pressing an Emergency Stop pushbutton or opening an interlocked safety gate NOT an acceptable substitute for Lockout/Tagout (LOTO) during maintenance?
Because E-Stops only work on DC circuits
Because OSHA forbids pressing E-Stops more than once per shift
Because safety gates cannot be wired to dual-channel relays
Because control-circuit devices do not physically disconnect energy sources and can be reset or bypassed while a technician is inside
Show the answer
D. Because control-circuit devices do not physically disconnect energy sources and can be reset or bypassed while a technician is inside
Under OSHA 1910.147(b), pushbuttons, selector switches, and interlocks are control-circuit devices, not energy-isolating devices. Servicing inside the hazard zone requires physically opening and locking the main electrical disconnect and pneumatic dump/lockout valve.